Solutions for Low Power Factor in Medium Frequency Furnaces/Industrial Furnaces
Time:
2019-01-05
Industrial Furnace Load: 1 unit of 75kW industrial furnace 1. Power Factor: The power factor is improved from around 0.58 to about 0.90, saving approximately 29% on electricity costs; 2. Filtering Effect: The 5th, 7th, and 11th harmonic currents are reduced from 29.7%, 6.5%, and 8.0% of the fundamental current to 4.1%, 4.2%, and 5.6%; 3. Device Features: The filtering effect is not affected by system parameters; compact structure, small size, suitable for on-site installation; 4. Supporting Components: LCD screen status.