Case Sharing | [New Materials Industry] Example Illustrating How Low Voltage Capacitor Compensation Cabinets Help Users Solve Low Power Factor and High Harmonic Issues


Time:

2019-11-18

Customer Name: Betterray (Jiangsu) New Materials Technology Co., Ltd. Harmonic Load: Roller Kiln Usage Location: Low Voltage Power Distribution System Purchased Equipment: Low Voltage Automatic Reactive Power Compensation and Harmonic Suppression Device TSCGD (Low Voltage Capacitor Compensation Cabinet) Low Voltage Capacitor Compensation Cabinet Design Plan Each transformer on the low voltage side is equipped with 3 compensation cabinets. Based on the client's situation and the detected data, the compensation under the transformer will be dismantled, modified, and upgraded. Each will install 1 set of low voltage automatic reactive power compensation and harmonic suppression device (low voltage capacitor compensation cabinet) to address the client's power factor and harmonic issues, improve the power factor, filter out characteristic sub-harmonics, and enhance power quality.

Customer Name:Better Energy (Jiangsu) New Materials Technology Co., Ltd.

Harmonic Load:Roller Kiln
Usage Location:Low Voltage Power Distribution System

Purchased Equipment:Welding Machine Dedicated Filter Compensation DeviceTSCGD(Low Voltage Capacitor Compensation Cabinet

Project Background

Better Energy (Jiangsu) New Materials Technology Co., Ltd. was established on January 16, 2017, and is a wholly-owned subsidiary of Shenzhen Better Energy New Materials Co., Ltd. Better Energy is the world's largest supplier of lithium-ion battery anode materials and the only company with a complete value chain for anode materials. It has led the formulation of several national standards such as 'Graphite Anode Materials for Lithium-Ion Batteries' and 'Carbon Composite Lithium Iron Phosphate Cathode Materials for Lithium-Ion Batteries'. Better Energy focuses on research and innovation, creating the industry's first and largest technology research institute for new energy materials, and is a global leader in the field of new energy materials.

Electricity Overview (Roller Kiln)

   According to on-site tests and information obtained from Better Energy in Changzhou, Jiangsu, there are currently 2 transformers with a rated capacity of 2500kVA, voltage level 10kV/0.4kV, with each transformer mainly loading a roller kiln, controlled by 3 distribution switches. The roller kiln is a typical nonlinear load that generates a large amount of harmonics during operation, primarily at the 3rd, 5th, and 7th harmonics, which severely affects the safe and stable operation of other electrical equipment. Harmonic treatment is required to prevent a large amount of high-order harmonics from feeding back into the upper-level power grid and to improve the quality of electrical energy.

Better Energy (Jiangsu) New Materials Technology Co., Ltd.

Low VoltageCapacitor Compensation CabinetDesign Plan

Each transformer is equipped with 3 compensation cabinets on the low voltage side. Based on the customer's situation and the detected data, the compensation under the transformer will be dismantled, modified, and upgraded. Each will install a set of welding machine dedicated filter compensation devices (low voltage capacitor compensation cabinets) to solve the customer's power factor and harmonic issues, improve the power factor, filter out characteristic sub-harmonics, improve the quality of electricity, and ensure the safety of production electricity.

Low VoltageCapacitor Compensation CabinetEffectAnalysis

After the operation of the welding machine dedicated filter compensation device TSCGD, the power factor increased from 0.58 to 0.96, meeting the requirement of maintaining a monthly average power factor between 0.91 and 0.97; the absolute value of the 3rd harmonic current decreased from 130A to 18.5A; the absolute value of the 5th harmonic current decreased from 255A to 58A; the absolute value of the 7th harmonic current decreased from 170A to 28.6A; the characteristic sub-harmonics were significantly reduced, with a harmonic current filtering rate of up to 75%, meeting the allowable values of GB/T14549-93; the total harmonic voltage distortion rate decreased from 4.5% to 2.5%, meeting national standard requirements, improving the quality of electrical energy, and ensuring safe operation.

Low VoltageCapacitor Compensation Cabinet Operating Data

Before operation, the total harmonic voltage distortion rate was4.5%

After operation, the total harmonic voltage distortion rate was2.5%

Before operation, the system power factor was 0.58

After operation, the system power factor was 0.96

 
 
 

Thank you for your visit

Guangda Electric's Thoughtful Suggestions:

Under the goodpower brand of Guangda Electric, we insist on providing sufficient value returns and feedback to every user who believes in us. To achieve stable product quality, we require Guangda people to inject 200% of their craftsmanship. In terms of material selection, we cannot afford mistakes, and in terms of craftsmanship, we do not allow laziness.

Dear customer, please rest assured of our craftsmanship, products, and services. We are committed to becoming a valuableLow Voltage Capacitor Compensation Cabinet Manufacturerand Reactive Power Compensation Harmonic Treatment Manufacturer.

Official Hotline: 18028173863

Guangda Electric Official Website:http://www.gd96.com/

Guangda Electric Official WeChat

Welcome to followGuangda ElectricOfficial WeChat

Power Quality

Customized Solutions

 

For more needs, please call Guangda Electric

18028173863

 

Long press to identify the QR code to followGuangda ElectricOfficial WeChat