The power factor of the medium frequency furnace has been improved to 0.92, allowing the foundry company to save 100,000 yuan in electricity costs per month.


User: Zhongtian Chuangzhan Ball Iron Co., Ltd. Name: Low Voltage Automatic Reactive Power Compensation and Harmonic Suppression Device Model: MSCGD-2920/0.75 Load: 1 unit of 5000kW medium frequency furnace 1. Power Factor: The power factor is improved from 0.77 to above 0.92, saving about 100,000 yuan in electricity costs per month, and reducing energy consumption per ton by 8.4%; 2. Filtering Effect: The 5th harmonic current is reduced to 13% of the fundamental current, and the 7th harmonic current is reduced to 7.6% of the fundamental current; 3. Temperature and Noise: The operating temperature and noise of the transformer are significantly reduced, allowing for full utilization of the transformer's capacity; 4. Supporting Components: Equipped with a liquid crystal display.


2025-02-13

How to use filters to improve harmonic issues during the operation of water pumps?


In the Shenzhen water plant, several variable frequency energy-saving pumps have been installed. 1. Power Factor: The power factor has improved from 0.86 to around 0.93, saving about 2% on electricity costs; 2. Filtering Effect: No faults have occurred since installation, and harmonic currents have significantly decreased, with the 5th harmonic reduced to 2.5% of the fundamental current; 3. Temperature and Noise: The pumps operate smoothly with no abnormal noise; the temperature and noise of the treatment devices are stable; 4. Supporting Components: An LCD screen is used for status display and human-machine interaction, providing an intuitive display.


2025-02-05

Solutions for Low Power Factor in Medium Frequency Furnaces/Industrial Furnaces


Industrial Furnace Load: 1 unit of 75kW industrial furnace 1. Power Factor: The power factor is improved from around 0.58 to about 0.90, saving approximately 29% on electricity costs; 2. Filtering Effect: The 5th, 7th, and 11th harmonic currents are reduced from 29.7%, 6.5%, and 8.0% of the fundamental current to 4.1%, 4.2%, and 5.6%; 3. Device Features: The filtering effect is not affected by system parameters; compact structure, small size, suitable for on-site installation; 4. Supporting Components: LCD screen status.


2025-02-13

How to solve the issue of harmonic distortion in the foundry causing the reactive power compensation cabinet to catch fire?


User: Yingde City Hanhua Fuda Casting Processing Plant Name: Outdoor High Voltage Automatic Reactive Power Compensation and Harmonic Suppression Device Model: MSCGD-5400/35 Load: Intermediate Frequency Furnace and Rolling Mill 1. Power Factor: The power factor is improved from 0.82 to about 0.92, saving about 4.5% on electricity costs; 2. Harmonic Suppression Effect: Stable operation without the risk of resonance; 3. Applicable Occasions: Maintenance-free outdoor compensation, saving infrastructure investment; 4. Device Features: Suitable for relatively stable loads; compact structure with small footprint; can achieve unattended operation. 5. Supporting Components: Uses an LCD screen for status display and human-machine interaction.


2025-02-13

Power Factor Solutions for Automotive Parts Processing Plants


The power factor solution for the automotive parts processing factory uses the MSCGD-4008/10, which has a compact structure and occupies a small space. The power factor is improved from 0.84 to around 0.92. If you have similar issues, you might want to learn more about Guangda's solutions.


2025-02-13

The power factor of the Shanghai hardware factory has been improved to 0.92, saving 40,000 yuan per month!


Hardware factory load: Equipment such as electric welding machines and lathes. 1. Power factor: The power factor has been improved from 0.84 to above 0.92, saving about 40,000 yuan in electricity costs per month; 2. Filtering effect: The 5th harmonic current has been reduced to 8.6% of the fundamental current, and the 7th harmonic current has been reduced to 6.3% of the fundamental current; 3. Temperature and noise: The operating temperature and noise of the transformer have significantly decreased, allowing for full utilization of the transformer's capacity; 4. Supporting components: An LCD screen is used for status display and human-machine interaction, addressing various needs.